MV Switchgear for Battery Energy Storage Systems: Key Design Considerations for BESS Projects in Australia
Updated: Aug 10
Battery Energy Storage Systems are becoming an increasingly important part of Australia’s electrical infrastructure. Utility-scale batteries, renewable energy projects, mining microgrids, industrial facilities, and network-support projects all rely on BESS to store energy, manage power flows, and support more flexible electrical operation.
Behind every large BESS is a medium voltage electrical system that must connect battery inverters, transformers, auxiliary systems, and the wider grid safely and reliably.
This makes MV switchgear for BESS a critical engineering and procurement decision.
Selecting BESS switchgear is not simply a matter of matching the system voltage.
Project teams must consider bidirectional power flow, short-circuit levels, inverter behaviour, protection coordination, switching duty, harmonic performance, transformer integration, auxiliary power, environmental conditions, SCADA requirements, and long-term maintainability.
For Australian EPC contractors, renewable developers, utilities, mining operators, consultants, and asset owners, getting these requirements right during specification can reduce commissioning risk and improve the reliability of the complete BESS installation.
Where Does MV Switchgear Fit Into a BESS?
A utility or commercial-scale BESS typically includes several major electrical components:
Battery racks or battery containers
Battery Management System (BMS)
Power Conversion System (PCS)
LV switchboards
Inverter or step-up transformers
MV switchgear
Protection and control systems
SCADA and Energy Management System (EMS)
Auxiliary power systems
Grid connection transformer or substation equipment
The exact architecture varies by project.
In many systems, the PCS converts DC battery power to AC at low voltage. A step-up transformer then increases the voltage to the project’s medium voltage collector level. MV switchgear connects individual BESS blocks or transformer feeders to the collector bus and, ultimately, to the grid connection point.
Leistung Energie’s MV switchgear portfolio includes primary and secondary equipment up to 40 kV, which is relevant to typical medium-voltage renewable and BESS collector applications.
Because BESS can both import and export power, the switchgear and associated protection system must be designed as part of a bidirectional electrical network rather than as a conventional one-way load feeder.
1. Start With the Electrical Architecture
Before specifying the switchgear, define the complete BESS single-line diagram.
The project team should establish:
BESS MW and MWh capacity
Number of battery blocks
PCS rating per block
Transformer rating per block
Nominal MV system voltage
Number of transformer feeders
Main busbar configuration
Grid connection arrangement
Auxiliary transformer configuration
Earthing arrangement
Future expansion requirements
Australian renewable projects commonly use MV collector voltage levels such as 11 kV, 22 kV, or 33 kV, depending on network connection requirements and project architecture.
The switchgear supplier should therefore receive more than a voltage level and panel quantity. A controlled single-line diagram, transformer data, cable information, protection philosophy, fault study data, and operating sequence provide a much better basis for equipment selection.
2. Select the Correct Voltage and Insulation Rating
The rated voltage of the switchgear must be coordinated with the nominal system voltage and the highest voltage expected under operating conditions.
The specification should define:
Nominal system voltage
Rated switchgear voltage
Insulation withstand level
Power frequency withstand voltage
Lightning impulse withstand level
System frequency
Earthing method
Indoor or outdoor installation
MV metal-enclosed switchgear falls within the scope of IEC 62271-200 for AC equipment above 1 kV and up to and including 52 kV, including indoor and outdoor installations.
The correct insulation rating should be confirmed against the project's insulation coordination study, network requirements, transformer data, surge protection philosophy, and site conditions.
3. Consider Bidirectional Power Flow
One characteristic that distinguishes BESS from a conventional load is bidirectional power flow.
During charging, power flows from the grid or renewable generation toward the battery. During discharge, power flows from the battery through the PCS and transformers back toward the MV network.
The switchgear busbar and primary conductors do not normally need different current ratings simply because power reverses direction. However, the overall system design must account for the maximum continuous current under both charging and discharging conditions.
The design should consider:
Maximum BESS import power
Maximum BESS export power
Reactive power operating range
Transformer rating
PCS overload capability
Simultaneous operation of multiple battery blocks
Ambient-temperature derating
Future expansion
Protection and metering require particular attention because directional behaviour may change depending on whether the plant is importing or exporting.
4. Calculate the Fault Level Before Selecting Switchgear
Short-circuit rating is one of the most important parameters in any MV switchgear for BESS specification.
The project fault study should determine the prospective fault current at every relevant MV bus.
Sources can include:
Utility or transmission network contribution
Upstream transformers
Parallel transformers
Synchronous generation, if present
Other connected renewable generation
BESS inverter contribution
Motors and industrial loads where applicable
BESS introduces an additional engineering consideration because inverter-based resources do not necessarily produce fault current with the same characteristics as synchronous machines. AEMO has highlighted the changing protection challenges associated with inverter-based resources and the importance of fault-current characteristics for reliable protection operation.
The switchgear specification should define:
Rated short-time withstand current
Short-circuit duration
Peak withstand current
Circuit breaker breaking capacity
Circuit breaker making capacity
Earth-fault level
Maximum future fault level where applicable
Do not select the switchgear fault rating solely from today's network conditions if planned network reinforcement or additional generation could increase fault levels during the asset life.
5. Protection Must Reflect BESS Operating Modes
Protection for BESS switchgear can be more complex than protection for a conventional radial feeder.
The protection philosophy may need to accommodate charging, discharging, standby operation, transformer energisation, grid disturbances, islanding scenarios, or grid-support functions depending on the project.
Typical protection functions may include:
Phase overcurrent
Earth fault
Directional overcurrent
Directional earth fault
Transformer differential
Restricted earth fault
Under-voltage
Over-voltage
Under-frequency
Over-frequency
Breaker failure
Trip circuit supervision
Synch-check where required
Arc protection
Interlocking
Anti-islanding functions where applicable
The final relay functions should come from the project protection study rather than from a generic switchgear schedule.
Coordination is required between the MV relay, PCS protection, transformer protection, BMS, EMS, upstream network protection, and grid connection requirements.
This is particularly important because existing power-system protection philosophies have historically been developed around fault characteristics produced by synchronous equipment, while inverter-based resources can respond differently during faults.
6. Understand the Actual Switching Duty
The term “battery charging and discharging cycles” can create confusion when switchgear is specified.
The MV circuit breaker does not necessarily open and close every time the battery changes between charging and discharging. Normal reversal of active power is typically controlled electronically by the PCS.
However, MV breakers may still perform important operational duties involving:
BESS block energisation
Transformer energisation
Fault interruption
Planned isolation
Maintenance switching
Emergency shutdown
Grid connection or disconnection
Testing and commissioning sequences
The breaker therefore needs to be evaluated for the actual number and type of switching operations expected throughout the asset life.
Transformer magnetising inrush, cable charging current, capacitive circuits, and any project-specific switching sequence should also be reviewed before final breaker selection.
7. Coordinate the Switchgear With the BESS Transformer
The transformer is one of the most important interfaces in a BESS electrical system.
Depending on the architecture, each PCS may connect to its own inverter transformer, several PCS units may share a transformer, or the collector system may feed a larger grid connection transformer.
The switchgear specification should coordinate with transformer parameters such as:
Rated MVA
Primary and secondary voltage
Vector group
Percentage impedance
Tap range
Inrush current
Cooling method
Transformer protection
CT requirements
Neutral arrangement
Earthing method
Transformer impedance is especially important because it influences fault levels and voltage performance.
Leistung Energie’s power transformer range is designed for applications including power generation, electric utilities, mining, oil and gas, water and wastewater, with designs available up to 500 kV insulation rating and 500 MVA depending on application.
For a BESS project, transformer and switchgear procurement should therefore be coordinated rather than treated as two unrelated equipment packages.
8. Account for Harmonics and Power Quality
BESS power conversion systems use power electronics. As with other inverter-based equipment, harmonic performance must therefore be considered as part of the complete system design.
The switchgear itself is not a harmonic filter, but harmonic current can influence the surrounding electrical system.
Project teams should review:
PCS harmonic spectrum
Total harmonic current distortion
Voltage distortion at relevant buses
Transformer harmonic heating
Cable loading
Capacitor bank interaction
Resonance conditions
Protection and metering accuracy
Grid connection harmonic limits
The analysis becomes particularly important where the site combines BESS with solar PV, VSDs, EV chargers, UPS systems, rectifiers, or other non-linear equipment.
Where harmonic mitigation is required, the solution should be selected from the actual harmonic study. Depending on voltage level and system architecture, this may involve inverter controls, transformer configuration, passive filtering, or active filtering at an appropriate point in the electrical system.
Leistung Energie also provides modular active harmonic filter solutions for LV applications, with filtering capability up to the 51st harmonic and support for automatic load balancing and compensation.
9. Do Not Overlook Auxiliary Power
A BESS cannot operate safely with only the main battery power conversion equipment.
A wide range of auxiliary loads may remain necessary whether the plant is charging, discharging, or in standby.
These can include:
Battery container HVAC
BMS equipment
EMS controls
PCS control power
Fire detection systems
Fire suppression systems
Communications
Network switches
Protection relays
Switchgear control circuits
Battery chargers
Lighting
Security systems
Monitoring equipment
The design should therefore determine how auxiliary power will be supplied during normal operation, shutdown, maintenance, and loss-of-grid conditions.
Depending on project criticality, this may require separate auxiliary transformers, DC systems, UPS supplies, redundant sources, or emergency backup.
MV switchgear specifications should identify auxiliary supply voltages and control power requirements early so that breaker mechanisms, protection relays, indication circuits, heaters, and communications are correctly configured.
10. Internal Arc Safety Remains Critical
BESS substations frequently use compact e-houses, prefabricated buildings, kiosks, or containerised electrical rooms.
Space efficiency is valuable, but compact layouts can make internal arc management more important.
The switchgear specification should consider:
Internal Arc Classification
Arc current
Arc duration
Front accessibility
Lateral accessibility
Rear accessibility
Pressure-relief design
Arc exhaust ducting
Switchroom ceiling height
Personnel access
Cable compartment arrangement
IEC 62271-200 provides the framework for metal-enclosed MV switchgear, including internal arc classification provisions.
For BESS e-houses in particular, the switchgear and building should be considered as an integrated safety arrangement. Pressure relief cannot be evaluated only at panel level without considering where hot gases would be directed.
11. Design for Australian Environmental Conditions
Many Australian BESS projects are located in environments that can be demanding for electrical equipment.
Conditions may include:
High ambient temperature
Solar heat load
Dust
Humidity
Salt contamination
Coastal corrosion
Remote locations
Condensation
Limited maintenance access
High daily temperature variation
These conditions should be documented in the equipment specification.
Depending on the site, project teams may need to define:
Enclosure protection level
Corrosion protection
Anti-condensation heaters
HVAC requirements
Maximum ambient temperature
Minimum ambient temperature
Altitude
Ventilation
Filtration
Outdoor enclosure requirements
Leistung’s existing renewable MV switchgear guidance also emphasises the importance of defining temperature, dust, humidity, corrosion exposure, ventilation, and enclosure conditions rather than specifying electrical ratings alone.
12. Earthing and Neutral Management Need Early Attention
The BESS earthing arrangement affects protection behaviour, earth-fault current, transformer selection, and switchgear specification.
The design should clearly define whether the MV system is:
Solidly earthed
Resistance earthed
Reactance earthed
Transformer-neutral earthed
Using a dedicated earthing transformer
Operated under another project-specific arrangement
Protection CT selection and earth-fault relay settings must be coordinated with the chosen grounding philosophy.
This should not be left until switchgear manufacturing has started. Changes to earthing arrangements can affect transformer connections, protection functions, CT ratios, cable design, and panel construction.
13. SCADA and BESS Control Integration
Modern BESS projects are highly automated.
The MV switchgear is therefore part of a larger control ecosystem connecting:
SCADA
EMS
BMS
PCS
Protection relays
Revenue meters
Power quality meters
Plant controller
Network operator interfaces
The specification should define required signals, including:
Breaker open/closed status
Breaker available status
Local/remote status
Protection trip
Relay alarms
Trip circuit healthy
Spring charged
Feeder voltage
Current
Active power
Reactive power
Power factor
Energy measurement
Fault records
Communication requirements may include IEC 61850, Modbus, DNP3, or another project-specific protocol.
The communication architecture should be confirmed before equipment manufacture so the relay, network interface, I/O count, control wiring, and cybersecurity requirements are properly coordinated.
14. Plan Cable Termination and Footprint Early
BESS projects can involve substantial cable quantities because multiple battery blocks may connect into the same MV collector system.
Project teams should define:
Cable size
Cable type
Number of cables per phase
Cable entry direction
Minimum bending radius
Cable termination height
Cable trench arrangement
Screen earthing
Surge arrester location
CT arrangement
A panel that is electrically rated correctly can still create major site problems if the cable compartment cannot physically accommodate the required terminations.
The overall switchroom footprint should also include:
Operating clearance
Maintenance access
Rear access where required
Arc duct clearance
Cable bending space
Lifting access
Panel extension space
This is especially important where the equipment is integrated into a prefabricated e-house.
15. Consider Future Expansion
Battery energy storage projects are often expanded in stages.
A project may initially install only part of the ultimate MW or MWh capacity and add additional battery blocks later.
If future expansion is possible, consider:
Spare switchgear panels
Extendable busbars
Busbar current capacity
Future transformer feeders
Protection relay capacity
SCADA I/O
Auxiliary supply capacity
Switchroom space
Cable routes
Increased future fault level
Providing appropriate expansion capacity during the initial design may be easier than modifying an energised MV switchboard later.
16. Testing and Documentation Are Part of the Equipment
For EPC, utility, and renewable projects, documentation quality can directly affect commissioning.
The MV switchgear package should specify requirements for:
Type test reports
Routine test reports
Factory Acceptance Test
General arrangement drawings
Single-line diagrams
Schematic diagrams
Wiring drawings
Interlocking diagrams
CT and VT schedules
Protection relay settings
Relay configuration files
Cable termination drawings
Communications architecture
Operation and maintenance manuals
Spare parts lists
Recommended maintenance schedules
Commissioning procedures
Leistung’s existing renewable switchgear guidance similarly identifies type tests, routine tests, FAT records, relay information, CT/VT details, drawings, manuals, and commissioning documentation as important procurement deliverables.
17. Lifecycle Support Matters for BESS Projects
BESS equipment is expected to operate as part of a long-term energy asset.
MV switchgear should therefore be evaluated based on more than purchase price and delivery time.
Ask suppliers about:
Local Australian technical support
Spare parts
Circuit breaker replacement options
Relay support
Training
Commissioning assistance
Maintenance intervals
Retrofit capability
Future extensions
Warranty
End-of-life support
This is particularly important for remote renewable and mining projects where an equipment failure can require significant travel, specialised personnel, and extended downtime.
Conclusion
Selecting MV switchgear for BESS projects requires more than choosing a voltage rating and circuit breaker.
Battery energy storage introduces bidirectional power flow, inverter-based fault behaviour, dynamic operating modes, transformer coordination, harmonic considerations, auxiliary loads, automation requirements, and potentially demanding environmental conditions.
For Australian BESS developers, EPC contractors, utilities, mining companies, and infrastructure owners, switchgear should therefore be engineered as part of the complete battery energy storage electrical system.
The best specification connects the PCS, transformer, MV network, protection system, SCADA architecture, auxiliary supply, and grid connection requirements into one coordinated design.
Getting those decisions right before procurement can help improve safety, simplify commissioning, reduce modification risk, and support reliable BESS operation over the full asset lifecycle.
Talk to Leistung Energie About MV Switchgear for Your BESS Project
Planning a battery energy storage project in Australia?
Leistung Energie Australia provides MV switchgear, power transformers, distribution transformers, and supporting power quality equipment for renewable energy, BESS, utility, mining, and infrastructure applications.
Contact the Leistung Energie team to discuss your BESS single-line diagram, voltage level, fault duty, protection requirements, transformer interface, environmental conditions, and lifecycle support needs before finalising your switchgear specification.




Comments